r
3.2.6.2.3 Air intake and flue
e system via 80/80 mm split pipes
C42 – C52 – C82 installation cate
th of air intake pipe is 1 meter.
Each wide radius 90° elbow (R=D) equals a 1 meter lon
pipe section.
Each narrow radius 90° elbow
equals a 1 meter long pipe section.
e
Minimum permissible length o
ue gas discharge pipe is 0,5 meter.
Each wide radius 90° elbow (R=D) in ue
pipe section.
Each narrow radius 90° elbow (R<D) in ue
m supplied with the boiler
7 diaphragm is supplied by the manufacturer in the optional air
ue gas split pipe kit
The above data are referred to air intake/flue
as exhaust systems which are implemented by means of smooth, ri
Pic. 13 - Dimensions for connection to the air intake/flue gas
exhaust split pipe system (CTFS)
Pic. 12 - Air intake/flue gas exhaust split pipe system (CTFS)