BOILER STATUS MALFUNCTION PROBABLE CAUSE SOLUTION
No. 1 led is ashing green and red.
The boiler will automatically resume
operation as soon as the malfunc-
tion is corrected.
DHW probe is not working
DHW probe is disconnected Reconnect it
DHW probe is faulty Replace it
Boiler is not supplying DHW
DHW ow meter is not working
System insufcient pressure or
ow rate
Check DHW system
Check DHW ow meter lter
DHW ow meter sensor is faulty or
disconnected
Replace or reconnect it
DHW ow meter sensor is blocked Replace it
No. 1 led is ashing green.
The boiler will automatically resume
operation as soon as the malfunc-
tion is corrected.
Gas valve modulation coil is not
working
PCB and gas valve link is discon-
nected or faulty
Check connection to the gas valve
Gas valve modulation coil is faulty Replace gas valve modulation coil