EasyManua.ls Logo

Novus N480D - Detailed Parameter Settings by Cycle; Operation Cycle Parameters; Tuning Cycle Parameters; Program Cycle Parameters

Novus N480D
6 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
N480D Controller
NOVUS AUTOMATION 3/6
OPERATION CYCLE
TEMPERATURE
INDICATION
Control Set
Point
When turned on, the controller indicates the process
temperature on the upper display. The lower display
shows the SP value, which is the desired temperature
for the process.
rate
Rate
Temperature increase rate. It allows the user to define
the increase or decrease characteristic of the process
programmed in SP. The rate is defined in Degrees per
minute.
minute.
It is available when the Rate option is selected in the
parameter of the Input cycle.
T SP
Adjustable from 0 to 9999.
It is available when the Rate option is selected in the
parameter of the Input cycle.
E pr
Enable
Program
Program Execution. It determines the cycle and ramp
program execution.
Executes program;
Does not execute program.
With enabled outputs (
=
program immediately enters in execution.
It is available when the Pr option is selected in the
parameter of the Input cycle.
Rvn
Run
Screen that enables or disables action of the
controller over the process. It acts as a switch, turning
the controller on or off.
Outputs enables;
Outputs not enabled.
TUNING CYCLE
Atvn
Auto tune
parameters (
,
,
). See chapter Auto tuning of
PID Parameters herein for more details.
Automatic tuning off;
Execute automatic tuning.
Pb
Proportional
band
control mode PID. In percentage of the maximum
span of the input type.
When set to zero (0), control action is ON/OFF.
Adjust of between 0 and 500.0 %.
Ir
Integral rate
mode PID, in repetitions per minute. This constant is
not used when controller is set to ON/OFF action
(
=
).
Adjustable between 0.00 and 55.20.
Dt
derivative time
. Value of the term
of the control
mode PID, in seconds. This constant is not used when
controller is set to ON/OFF action (
=
).
Ajustable between 0 and 250.
(t
Cycle time
CYCLE TIME. Pulse Width Modulation (PWM) period
in seconds. This constant is not used when controller
is set to ON/OFF action (
=
).
Adjustable between 0.5 and 99.99
KySt
HYSterisis
CONTROL HYSTERESIS. Hysteresis for ON/OFF
control (set in temperature units).
This parameter is only used when the controller is in
ON/OFF mode (
=
).
A1SP
A2SP
Alarm SP
SETPOINT FOR ALARM 1 AND 2. Tripping point for
alarm 1 and 2.
PROGRAM CYCLE
Ptol
Program
Tolerance
Maximum admitted deviation of PV with respect to SP. If
exceeded, the program execution is suspended (the
internal timer freezes) until the deviation be returns back
within the defined tolerance.
The value 0 (zero) disables the function.
Psp0
Psp9
Program SP
Program SP’s, 0 to 9. Group of 10 values of SP that
define the Ramp and Soak profile segments.
Pt1
Pt9
Program Time
Time intervals of the program segments. It defines the
duration in minutes, of each of the 9 program
segments. Configurable between 0 and 9999 minutes.
Pe1
Pe9
Program
event
Program segment alarm (Event Alarm). Parameters
that define the alarm must be activated during the
execution of a certain program segment:
OFF
Do not activate alarm in this segment.
A1
Activate alarm 1 when program reaches this
segment.
A2
Activate alarm 2 when program reaches this
segment.
A1A2
Activate alarms 1 and 2 when program
reaches this segment.
The alarms chosen must have its function configured
as “
rS
”.
rPt.P
Repeat
Program
It determines the number of times the program must be
REPEATED, besides the initial execution. Configurable
between 0 and 9999 times. After the last execution, all
controller outputs are turned off (RUN = OFF).
INPUT CYCLE
Type
tYPE
INPUT TYPE. Selects the input signal type to be
connected to the process variable input. Refer to
Table 1 for the available options.
This must be the first parameter to be configured.
Dp.po
Decimal Point
DECIMAL POINT. Defines the decimal point position.
Vnit
unit
UNIT. Defines the indication unit in Celsius or
Fahrenheit.
(
Celsius degrees (°C);
F
Fahrenheit degrees (°F);
A(t
ACtion
CONTROL ACTION
:
re
Reverse action. Generally used for
heating.
Dir
Direct action. Generally used for
cooling.
Ovt.a
Ovt.b
Ovt.(
Ovt.d
OUTA, OUTB, OUTC and OUTD function:
Off
Output not used;
(trl
Output defined as control output;
A1
Output defined as alarm output 1;
A2
Output defined as alarm output 2;
(.0.20
Output defined as control output 0-20
mA (only for OUTD);
(.4.20
Output defined as control output 4-20
mA (only for OUTD).
spll
SP Low Limit
SETPOINT LOW LIMIT.
Selects
minimum
adjustment for parameters relative to the SP (
SP
,
A1SP
,
A2SP
).
spKl
SP High Limit
SETPOINT HIGH LIMIT. Selects maximum
adjustment for parameters relative to the SP (
SP
,
A1SP
,
A2Sp
).

Related product manuals