EasyManua.ls Logo

NTI Trinity TX51 - Outdoor Sensor; Boiler Address; System Sensor; Minimum Pipe Sizes for Multiple Boiler Applications

NTI Trinity TX51
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cascade Instructions Tx I&O Manual
System Sensor install a system sensor (NTI P/N: 84010) on the outlet (supply) pipe feeding the heating system,
see Figure 13-1. Wire the system sensor to terminals 3 and 4 of the Managing Boiler (left boiler in illustration).
IMPORTANT: the use of the system sensor is mandatory for proper operation of the boiler cascade system.
Outdoor Sensor when using an outdoor sensor it must be connected to terminals 3 and 5 of the Managing
boiler (left boiler in illustration); outdoor sensors connected to non-Managing boilers will be ignored.
Boiler Pump each boiler in the cascade must have its own circulator (see Figure 13-1) which is operated by
each respective boiler, via the BOILER PUMP output (terminal 11). The Boiler Pump must be sized according to
Table 10-4.
CH Pump the Managing Boiler can control the Central Heating Pump via its CH PUMP output (terminal 10).
IMPORTANT: due to the limited switching capacity of the CH PUMP output, it may be necessary to use an
isolation relay to activate the CH Pump, see Table 12-1.
DHW Pump the Managing Boiler can control the DHW Pump via its DHW PUMP output (terminal 9).
IMPORTANT: due to the limited switching capacity of the DHW PUMP output, it may be necessary to use an
isolation relay to activate the DHW Pump, see Table 12-1.
Central Heat Demand Switch (Room Thermostat) connect to terminals 7 and 8 (T, T) of the Managing
Boiler. Switch must be an isolated end switch (dry contact). Central Heat settings are programed from the
Managing Boiler only, i.e. Installer menu settings 2-01, 2-02, 2-03, 2-04, 2-05 and 2-06.
Tank Thermostat / Sensor connect to terminals 3 and 6 of the Managing Boiler. DHW settings are programed
from the Managing Boiler only, i.e. Installer menu settings 2-07, 2-08 and 2-09. Set DHW Mode (Installer menu
setting 2-08) according to device used; Thermostat = 2, Sensor = 1.
Boiler Address assign a unique boiler address for each boiler in the cascade via Installer menu setting 2-20.
Managing boiler must be set = 1; other boilers must be set from 2 to 16.
Rotation Interval establishes the time, in days, between advancements of the staging sequence of boilers in the
cascade; set via Installer menu setting 2-22 of the Managing Boiler.
Emergency Setpoint establishes an emergency (back-up) boiler operating setpoint in the event communication
is lost between boilers, or if the system sensor is not connected. Set via Installer menu setting 2-21 of each boiler
in the cascade.
Table 13-1 Minimum Pipe Sizes for Multiple Boiler Applications
# of Units
Tx51
Tx81
Tx101
Tx151
Tx200
Pipe Size
Pipe Size
Pipe Size
Pipe Size
Pipe Size
2
1”
1-1/4”
1-1/4”
1-1/2”
2”
3
1-1/4”
1-1/2”
1-1/2”
2”
2”
4
1-1/4”
1-1/2”
2”
2”
2-1/2”
5
1-1/2”
2”
2”
2-1/2”
2-1/2”
6
1-1/2”
2”
2”
2-1/2”
3”
7
1-1/2”
2”
2-1/2”
2-1/2”
3”
8
2”
2”
2-1/2”
2-1/2”
4”
9
2”
2-1/2”
2-1/2”
3”
4”
10
2”
2-1/2”
2-1/2”
3”
4”
11
2”
2-1/2”
2-1/2”
3”
4”
12
2”
2-1/2”
2-1/2”
3”
4”
13
2”
2-1/2”
3”
3”
4”
14
2”
2-1/2”
3”
4”
5”
15
2”
2-1/2”
3”
4”
5”
16
2-1/2”
3
3”
4”
5”
Note: Minimum pipe size based on assumed temperature rise of 25ºF at maximum firing rate.

Table of Contents

Related product manuals