6002 addressable control and indicating equipment
User Manual
12
31-0019-r04_2018-08
© 2017, 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
All specifications and other information were current at the date of publication and subject to change without notice.
QUEUE REVIEW TEST LED will flash. The cursor will move to the next zone number for further selections.
8) When complete, press to return to the menu.
9) Press the LAMP TEST button to toggle the selected zone in and out of Test Condition.
10) The selected zone FAULT TEST DISABLE LED and the QUEUE REVIEW TEST LED will flash.
11) Test each initiating device within the zone.
12) Check that the initiating device indicator is on, that the fire signal is displayed on the LCD for 15 s, and
that the audio/visual alarm devices operate for 1 s (if configured).
Un-zoned Initiating Device Tests
To test a device not assigned to a detection zone, test each initiating device. Check that the initiating device
indicator is on, that the fire signal is display on the LCD, and that the audio/visual alarm devices operate.
3.7.3. Audio/Visual Alarm Device Test
For minimal disruption in an occupied building, audio/visual alarm devices can be activated for 1 s, followed
by silence for 9 s. Menu Item 6-2 provides an alternative to testing using the ALARMS ACTIVATE/SILENCE
button.
Test All
To test all audio/visual alarm device, press the ALARMS ACTIVATE/SILENCE button.
Specific Tests
Audio/visual alarm devices can be configured into groups and conditionally operate depending on other
configuration settings, such as delay timer settings and fire detection within specific zones. To test individual
alarm devices or groups of alarm devices, review the configuration settings and prepare a specific test plan.
3.7.4. Multiple Test Conditions
If one or more devices or zones are in the test mode, the FAULT TEST DISABLE LED the QUEUE REVIEW
TEST LED will flash. Press the TEST button to display the Test Conditions. After the Test Conditions have been
displayed, the QUEUE REVIEW TEST LED will be on steady.
After 15 s, the LCD will revert to the previous display.
3.8. System Reset
To reset the fire detection and alarm system, undertake the following the steps.
1) Insert the key and enable the controls. The CONTROLS ACTIVE LED will be on steady.
2) Enter Access Level 2 or Access Level 3.
3) Press the SYSTEM RESET button. After the control and indicating equipment finishes initializing, the
internal sounder will operate. Any Conditions still active will be displayed.
4) Press the BUZZER SILENCE button to silence the internal sounder.