2.3. Access Level 3 (Installer Access)
Access Level 3 is used to configure the control and indicating equipment and connected devices (see
section 9).
2.3.1. Enter Access Level 3
To enter Access Level 3, undertake the following actions.
1) Press the
button. The LCD will prompt to enter the Access Level 2 passcode.
2) Enter 4 5 6 7 8.
3) Press the
button to confirm the passcode.
The LCD will display Installation Access Level and prompts to navigate through the Menu Items.
Access Level 3 allows unlimited input attempts, however the entry sequence must start within 10 s and there
must be no more than 5 s between key presses. If these times are exceed, the control and indicating equipment
will revert to Access Level 1.
2.3.2. Change Access Level 3 Passcode
The Access Level 3 passcode can be changed from the default settings. The Access Level 3 passcode is
configured using the alpha-numeric keypad. To change the Access Level 3 passcode, undertake the following
actions.
1) Enter Access Level 3.
2) Select Menu Item 7-3-4.
3) Use the alpha-numeric keypad to enter the existing 5-digit Access Level 3 code.
4) Press
to confirm.
5) Enter the new 5-digit Access Level 3 code.
6) Press
to confirm.
7) Confirm the new 5-digit Access Level 3 code.
8) Press
to confirm and return to the menu.
2.4. Access Level 4 (Engineer Access)
Access Level 4 is used to restore the factory default settings, and is rarely required. Where restoration is
required, contact Numens Customer Service.
Changes made at Access Level 3 affect the factory default settings and the
operation of the system. Changes should only be made by qualified personnel who
are fully aware of their effects.
If an Alarm Condition or Fault Condition has occurred, the conditions must be
acknowledged before entering Access Level 3. Access Level 3 can only be accessed
when the control and indicating equipment has no unacknowledged events.