Copyright © 2016 Broan-NuTone LLC 17
Feature Description Range
Default
Setting
Heat - Cool
Delta
Sets the minimum separaon between heang and
cooling setpoints. NOTE: Attempts to lower
cooling setpoint below the heating setpoint
will PUSH the heating setpoint down to
maintain this separation. The same applies to
setting the heating setpoint above the cooling
setpoint; it will PUSH the cooling setpoint up
to maintain the setpoint delta separation.
3 to 15
degrees
3F (1C)
Heang Stage
1 on Threshold
Sets the delta from setpoint that stage 1 heang starts. 1 to 6
degrees
1
Heang
Stage 1 O
Threshold
Sets the delta from setpoint that stage 1 heang stops.
Stage 1 turns o at setpoint + Delta Stage 1.
0 to 5
degrees
0
Heang
Stage 2 On
Threshold
Sets the delta from setpoint that stage 2 heang starts. 2 to 7
degrees
2
Heang
Stage 2 O
Threshold
Sets the delay from setpoint that stage 2 heang stops.
Stage 2 turns o at setpoint + Delta Stage 2.
0 to 6
degrees
0
Aux Heat On
Threshold
Sets the delta from setpoint that stage 3 heang starts. 3 to 8
degrees
3
Aux Heat O
Threshold
Sets the delta from setpoint that stage 3 heang stops.
Stage 3 turns o at setpoint + Delta Stage 3
0 to 7
degrees
0
Cooling
Stage 1 On
Threshold
Sets the delta from setpoint that stage 1 cooling starts. 1 to 7
degrees
1
Cooling
Stage 1 O
Threshold
Sets the delta from setpoint that stage 1 cooling stops.
Stage 1 turns o at setpoint - Delta Stage 1.
0 to 6
degrees
0
Cooling
Stage 2 On
Threshold
Sets the delta from setpoint that stage 2 cooling starts. 2 to 8
degrees
2
Cooling
Stage 2 O
Threshold
Sets the delta from setpoint that stage 2 cooling stops.
Stage 2 turns o at setpoint - Delta Stage 2.
0 to 7
degrees
0
Restore
Defaults
Restores all sengs to factory defaults.
Press Yes to restore defaults.
Press No to exit and not restore defaults.
Y or N N