34
616 01 1017 02
Auto Mode Enable
When Auto Mode is enabled (factory default) a change from
heat to cool (or vice versa) will not occur until the current
cycle is satisfied and an opposite mode demand has existed
for 30 minutes. If the setpoint is changed, the 30 minute
timer is deleted.
On – Auto mode is available
Off – Auto Mode is not available
Default = On.