for 30 minutes. If the setpoint is changed, the 30 minute
timer is deleted.
Enable/Disable Auto Changeover mode (default = En
able).
Auto Changeover Time may be adjusted 5 to 120 minutes,
(default = 30 minutes).
Setpoint Deadband
The minimum difference enforced between heating and cool
ing desired temperatures. This can allow one setting to
“push” the other to maintain this difference.
0 to 6ºF (0 to 3ºC), (default = 2ºF)
Offsets
This option allows calibration (or deliberate miscalibration)
of the temperature and humidity sensors. These offsets are
added to the actual temperature/humidity values (default =
0).
Temperature Offset: 5ºF to +5ºF (3ºC to +3ºC)
Outside Temp Offset: 5ºF to +5ºF (3ºC to +3ºC)
Humidity Offset: 10 to +10%
Cycles Per Hour
Maximum cycles per hour = 4 (default) or 6.