Descrizione Description Unità di
misura
Measuring
unit
Minimo
Minimum
Massimo
Maximum
Valore
Value
A05 - Durata input uss.
off per disatt. all.
A05 - Flow switch off input
duration for alarm deactivation
s 0 255 15
A07 - By-pass termica da
attivaz. comp.
A07 - Thermal switch bypass
from compressor activ.
Min 0 255 15
A09 - Eventi/h all. vent.
switch riarmo man.
A09 - Fan alarm events/hour,
man. reset switch
Min 0 255 2
A10 - By-pass all. antig.
da ON-OFF macchina
A10 - Antifreeze alarm bypass
from machine’s On-Off
Min 0 255 2
A11 - Setpoint allarme
antigelo
A11 - Antifreeze alarm
setpoint
°C -127 127 3
A12 - Isteresi allarme antigelo A12 - Antifreeze alarm hysteresis °C 0 25,5 2
A14 - Setpoint allarme alta
pressione
A14 - High pressure alarm
setpoint
°C
/10
-KPa*10
0 900 900
A16 - Bypass all. bassa
in. analg. da ON comp.
A16 - Low alarm bypass,
analog input, from ON comp.
s 0 255 255
A17 - Setpoin allarme bassa
pressione
A17 - Low pressure alarm
setpoint
°C
/10-
KPa*10
-500 800 -500
A19 - Eventi/h all. bassa switch
a riarmo man.
A19 - Low alarm events/hour,
switch to manual reset
Num 0 255 255
A20 - Diff. inizio conteggio
macchina scarica
A20 - Count start diff., empty
machine
°C 0 25,5 0
A21 - By-pass count macc.
scarica da ON comp.
A21 - Count bypass, empty
machine, from comp. ON.
Num 0 255 255
A22 - Durata macchina scarica A22 - Empty machine duration Num 0 255 255
A23 - Attivazione allarme
macchina scarica
A23 - Empty machine alarm
activation
Flag 0 1 0
A25 - Set over temperature ST1 A25 - Set over temperature ST1 °C 0 255 80
A26 - Durata ON over-tempe-
rature
A26 - Over-temperature
duration ON
s*10 0 255 20
C01 - Delay OFF-ON
compressore
C01 - Compressor OFF-ON
delay
s*10 0 255 18
C02 - Delay ON-ON
compressore
C02 - Compressor ON-ON
delay
s*10 0 255 36
C03 - Isteresi termoregolatore
in cooling
C03 - Thermoregulator
hysteresis in cooling
°C 0 25,5 3
F01 - Congurazione uscita
ventole
F01 - Fan output conguration Num. 0 3 33
F02 - Tempo spunto ventilatore F02 - Fan speedup time Num. 0 3 30
F04 - Durata impulso
accensione triak
F04 - Triak starting impulse
time
uS*10 0 255 5
F05 - Dipendenza del vent.
da ON comp.
F05 - Fan dependence on
comp. ON
ag 0 1 0
F25 - Preventilazione in cool F25 - Preventilation in cool s 0 255 5
P01 - Modo operativo pompa P01 - Pump operating mode Num. 0 4 0
P02 - Ritardo ON pompa da ON
compressore
Pump ON delay from
compressor ON
s 0 255 20
P03 - Ritardo OFF compressore
da OFF pompa
P03 - Compressor OFF delay
from pump OFF
s 0 255 20