OIL PRIMARY CONTROL  SEQUENCE OF OPERATION
Oil Primary Control Detailed Sequence of Operation
Power is applied to unit. e oil primary control completes a self-
diagnostic procedure. If no light or ame is present, and unit passes
its self-diagnostic procedure, the control enters into the idle mode.
ermostat calls for heat:
Safety check is made for ame (4 second delay).
1.
If ame is not present, the oil primary control will apply A.
power to the burner motor and igniter.
If ame is present, the control remains in the idle state.B.
Unit enters a pre-purge period of 15 seconds.
2.
Aer 10 seconds, control checks for ame presence.
3.
If ame is not present, the oil primary control enters the A.
trial for ignition state.
When ame is present, the control enters lock out mode. B.
e Oil Primary Control monitors the burner ame.
4.
When ame is present, the control enters ignition carry-A.
over state. (Continues to spark for 10 sec.).
Provides continuous spark aer ame is sensed to assure •
that burner remains lit.
Turns on LED diagnostic light.•
Starts carryover timer.•
a) Flame and call for heat are monitored.
■ If ame is lost and lockout timer has not expired,
the control will return to trial for ignition state.
■ If ame is lost and lockout timer has expired, the
control will enter the recycle state.
Recycle timer starts.•
Burner motor and igniter and solenoid •
valve are turned o.
LED diagnostic light ashes slowly.•
Carryover timer expires.
5.
Enters run state.A.
Igniter turns o.•
Combustion continues until thermostat is satised, or the oil pri-
mary control detects a loss of ame and enters into Recycle Mode.
ermostat is satised - call for heat is terminated:
6.
Oil primary control shuts o burner motor and solenoid A.
valve.
If the control utilizes a blower motor o delay, aer 30 •
seconds, ame presence is checked.
■ If ame is not present, the control LED diagnostic
light is o and returns to idle state.
■ If ame is presence is detected, the control enters
lock out mode.