CT Analyzer User Manual
174
210.xxx Warning [210.xxx] Permanent data overflow.
Reason: Internal data buffer overflow. The data could not be fetched fast enough from
the internal data buffer.
Solution: Try to repeat the measurement. If this error occurs more frequently, you should
contact your next OMICRON service center.
211.xxx Warning [211.xxx] AC mode measurement timeout.
Reason: Measurement timeout due to frequent range switching or invalid data from the
measurement inputs.
Solution: Check the wiring and repeat the measurement. Try to reduce noise for the
measurement.
220.xxx Warning [220.xxx] Test aborted!
Reason: The test sequence has been interrupted by the user.
Solution: Repeat the test without interrupting it.
308.xxx Note [308.xxx] I-sn value has to be specified in CT-Object Card prior to Residual
Magnetism test!
Reason: For the remanence test the I
sn
value should be defined.
Solution: Enter valid I
sn
value before starting the remanence test.
310.xxx Note [310.xxx] License: <Guesser functionality> is missing! Values for: Ipn, Isn, P/M,
Class, FS/ALF should be provided.
Reason: The license required for class guessing is not available.
Solution: Specify the values for I
pn
, I
sn
, Class, P/M and FS/ALF before starting the test.
311.xxx Warning [311.xxx] License: <Simulation after test> is missing!
Reason: The license required for simulation is not available.
Solution: Simulation of the results for changed test settings (e.g. different burden values)
after the test is not possible. Purchase a corresponding license.
312.xxx Warning [312.xxx] License: <...> is missing!
Reason: The license specified in the message is not available.
Solution: The functionality included in the license is not available. Purchase a
corresponding license.
313.xxx Warning [313.xxx] License: <All languages> is missing! Test can be performed only if
the Chinese user interface is set.
Reason: The license required to use all languages is not available.
Solution: Perform the test with the Chinese user interface or purchase a corresponding
license.
318.xxx Warning [318.xxx] License: <Burden guesser> is missing! Values for VA, Burden, Cos
ϕ
should be provided.
Reason: The license required for the burden guesser functionality is not available.
Solution: Specify the values for nominal and operating burden (VA, Burden and cos
ϕ) or
purchase a corresponding license.
319.xxx Warning [319.xxx] License: <Quick test> is missing!
Reason: The license required for the Quick Test functionality is not available.
Solution: Purchase a corresponding license if you want to perform measurements using
Quick Test.
331.xxx Note [331.xxx] Ipn is invalid! The value must be between the Ipn values of the
neighboring taps.
Reason: An invalid I
pn
value has been entered to the MR-Config. card.
Solution: Enter a valid I
pn
value.