CT Analyzer User Manual
180
824.xxx Error [824.xxx] An internal software error has occurred at address xxxxxxxH. To log
this error, make sure that a CF card is inserted and then press OK. Please send the file
\OMICRON\ErrorLog.xml on the CF card to the next OMICRON service center.
Reason: Invalid result in a floating point operation (NaN).
Solution: Contact your next OMICRON service center.
825.xxx Warning [825.xxx] Size of file [FileName] >= 1Mbyte.
Reason: The size of the file copied to the CT Analyzer Compact Flash card or virtual disc
is > 1 MB.
Solution: Avoid transfer of large files > 1 MB to the CT Analyzer.
830.xxx License < ... > is invalid.
Reason: An invalid license entry was found in the license file Omicron.lic on the CF
Card.
Solution: Specify a valid license key.
831.xxx Setting value for < ... > is invalid. The default value of < ... > is used.
Reason: Invalid item in file Settings.inf.
Solution: The file Settings.inf in the Omicron directory on the CF card of the
CT Analyzer has a formatting error in one of the parameters. Delete this file and
check the settings in the menu Main Menu -> Settings -> Misc. Settings. If
necessary, change the settings and store the file again.
832.xxx Lifetime of relays near end. Contact the next OMICRON service center soon to arrange
a hardware service.
Reason: The relays inside the CT Analyzer near the end of their lifetime (more than
1,000,000 measurements performed).
Solution: Arrange a hardware service in order to replace the relays.
833.xxx You are about to load a report with an invalid hash code. Some measurement values
may not be authentic.
Reason: The file checksum is not valid.
Solution: Check the authenticity of the report file loaded.
834.xxx No valid license was found in this file!
Reason: No valid license found.
Solution: Check the license file. The license possibly does not correspond to the serial
number of the CT Analyzer.
835.xxx Downgrade a firmware below version 3.53 is not supported.
Reason: Attempt for a downgrade to a version number < 3.53.
Solution: Make sure that die FW version number for the upgrade/downgrade is not below
3.53.
900.xxx Error [900.xxx] Power supply error. Switch off the device and wait 1 minute to restart.
Reason: The output power was larger than 350VA or the power supply is defective.
Solution: Switch the CT Analyzer off, wait 1 minute and then switch it on again. If this
error occurs more frequently, you should contact your next OMICRON service
center.