503
Execution Conditions
Commands Responses
Single Multiple Single Multiple
---
--- OK ---
End Codes There are no end codes with this command.
10-3-40 Undefined Command –– IC
This response is returned if the header code of a command cannot be decoded.
Check the header code.
Response Format
@ IC
x 10
0
x 10
1
Node no. Header
code
TerminatorFCS
Limitations This error response will be returned if there are fewer than 6 bytes of data be-
tween a command’s “@” character and the terminator, an incorrect header code
is used, or a frame is corrupted.
There is no command associated with IC.
PC Settings
PC Mode UM Area
RUN MONITOR PROGRAM Write-protected Read-protected
OK OK OK OK OK
Execution Conditions
Commands Responses
Single Multiple Single Multiple
---
--- OK ---
End Codes There are no end codes with this command.
Host Link Commands
Section 10-3