4-9
4 Determining IP Addresses
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
4-2 Setting the IP Address of the EtherNet/IP Unit
4
4-2-3 Online Connection
Precautions for Correct UsePrecautions for Correct Use
If the IP address is duplicated or not set correctly, communications are not possible via the
EtherNet/IP network.
The IP address range shown below is used by the system and cannot be specified.
169.254.0.0 to 169.254.255.255
192.168.255.0 to 192.168.255.255
Due to Ethernet restrictions, you cannot specify the IP addresses that are described below.
An IP address that is all 0’s or all 1’s
IP addresses that start with 127, 0, or 255 (decimal)
An IP address with a host ID that is all 0’s or all 1’s
An IP address with a network ID that is all 0’s or all 1’s
Class-D IP addresses (224.0.0.0 to 239.255.255.255)
Class-E IP addresses (240.0.0.0 to 255.255.255.255)
Connecting from a Saved Project
The connection configuration that is set (USB or EtherNet/IP) is saved in the project. (The file is
xxx.smc.) If you open a saved project on the Sysmac Studio, you can connect to the EtherNet/IP
network without redoing the settings.
Checking the Current IP Address
You can use the following device variable for the CJ-series Unit to check the IP address that is set for
the EtherNet/IP Unit.
The IP address is stored as shown below.
Device variable name for CJ-
series Unit
Data
type
R/W Meaning Description
*_IPAdrCfg DWORD RW IP address dis-
play/setting area
Default: 00000000
*_IPAdr1Cfg USINT RW IP Address 1 Part (1) of the IP Address of the Eth-
erNet/IP Unit
*_IPAdr2Cfg USINT RW IP Address 2 Part (2) of the IP Address of the Eth-
erNet/IP Unit
*_IPAdr3Cfg USINT RW IP Address 3 Part (3) of the IP Address of the Eth-
erNet/IP Unit
*_IPAdr4Cfg USINT RW IP Address 4 Part (4) of the IP Address of the Eth-
erNet/IP Unit
First byte
Byte
First byte + 1
IP Address: (1).(2).(3).(4) (hex)
(1)
(2)
(3)
(4)
1514131211109876543210