1-13
1 Introduction
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
1-3 EtherNet/IP Unit
1
1-3-2 Part Names and Functions
Example 2: Displaying Multiple Error Sources
• A d6 error (failed to establish connection) occurred with IP address 192.168.250.8.
• A d6 error (failed to establish connection) occurred with IP address 192.168.250.9.
• A d5 error (verification error, target nonexistent) occurred with IP address 192.168.250.64.
• A C6 error (multiple switches ON) and EA error (EtherNet/IP Advanced Setting Error) occurred at
the local EtherNet/IP Unit, IP address 192.168.250.10.
There is no particular priority to the order in which the errors are displayed. All of the errors are dis-
played repeatedly in order.
The error code is displayed and then the last digit of the target node's
IP address is displayed in hexadecimal.
Displays errors that occurred
within the Unit.
The last digit of the Unit's IP address
is displayed in hexadecimal.