110
Adjustment Level Section 5-4
This parameter sets the current for the heater burnout alarm to be output.
• The heater burnout alarm is output when the heater current value falls
below the setting of this parameter.
• When the set value is 0.0, the heater burnout alarm is turned OFF. When
the set value is 50.0, the heater burnout alarm will turn ON.
Related Parameters
Heater current 1 value monitor (adjustment level): Page 109
HB ON/OFF: Page 135, Heater burnout latch, Heater
burnout hysteresis:
Page 136
(advanced function setting level)
This parameter sets the current for the HS alarm to be output.
• The HS alarm is output when the leakage current value goes above the
setting of this parameter.
• When the set value is 50.0, the HS alarm is turned OFF. When the set
value is 0.0, the HS alarm will turn ON.
Related Parameters
Leakage current 1 monitor (adjustment level): Page 109
HS alarm use, HS alarm latch: Page 143, HS alarm hysteresis: Page 144
(advanced function setting level): Page 143
hb1 Heater Burnout Detection 1
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The “heater burnout detection”
parameter must be set to ON.
Setting range Unit Default
0.0 to 50.0 A 0.0
Function
Setting
See
See
hs1 HS Alarm 1
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The “HS alarm” parameter must be
set to ON.
Setting range Unit Default
0.0 to 50.0 A 50.0
Function
Setting
See
See
■
■