Explicit Messages Specific to DeviceNet-compatible Digital Controllers Section 5-3
Explicit Message
Communications
5-3-1 Reading General Status
5-3-2 Writing Maintenance Mode Data
5-3-3 Setting and Monitoring the Digital Controller Channels
Explicit
message
Read/
write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data
size
General
Status
Read
Read Reads the DeviceNet-com-
patible Controller’s general
status bits (8 bits). (Refer
to page 4-11).
0E hex 95 hex 01 hex 65 hex --- 1 byte
Explicit
message
Read/
write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data
size
Mainte-
nance
Counter
Save
Save Records the maintenance
counter (PV of total ON/
RUN time for all Digital
Controllers) in memory.
16 hex 95 hex 01 hex 75 hex --- ---
Explicit
message
Read/
write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data size
Digital Con-
troller
Channel
Mainte-
nance Infor-
mation
Monitor
Mode
Read Reads the monitor
mode for maintenance
information of the Digi-
tal Controller channel
(see note 1) specified
by the Instance ID (1 to
4).
0E hex 7A hex 01 to 04
hex
65 hex 1 byte
00 hex: Unit
conduction
time mode
01 hex: Total
RUN time
mode
Write Writes the monitor
mode for maintenance
information of the Digi-
tal Controller channel
(see note 1) specified
by the Instance ID (1 to
4).
10 hex 7A hex 01 to 04
hex
65 hex 1 byte
00 hex: Unit
conduction
time mode
01 hex:
Total RUN
time mode
Set Value
for Unit
Conduction
Time or
Total RUN
Time
Read Reads the set value
(monitor value) for the
Unit conduction time or
total RUN time (unit: s)
of the Digital Controller
channel (see note 1)
specified by the
Instance ID (1 to 4).
0E hex 7A hex 01 to 04
hex
68 hex 4 bytes
00000000 to
FFFFFFFF
hex (0 to
4294967295)
Write Writes the set value
(monitor value) for the
Unit conduction time or
total RUN time (unit: s)
of the Digital Controller
channel (see note 1)
specified by the
Instance ID (1 to 4).
10 hex 7A hex 01 to 04
hex
68 hex 4 bytes
00000000
to
FFFFFFFF
hex (0 to
429496729
5)