7-2
Indicators and Error Processing Section 7-1
Troubleshooting
and Maintenance
7-1 Indicators and Error Processing
The following table lists the indicator status when errors occur, the probable
causes and processing.
Indicator status Probable cause Remedy
MS: OFF
NS: OFF
The power is not being
supplied to the Control-
ler.
Supply communications power from
the DeviceNet connector.
The power voltage is
not within the permitted
range.
Use a power supply voltage within the
permitted range.
The Controller is faulty. Replace the Controller.
MS: Flashing red
NS: No change
A checksum error has
occurred in the parame-
ters registered in
EEPROM.
Repairs are required if this error per-
sists even if the parameters are reset.
Contact your nearest OMRON repre-
sentative.
A EEPROM hardware
error has occurred.
MS: ON red
NS: OFF
The Digital Controller is
faulty
Repairs are required. Contact your
nearest OMRON representative.
MS: ON green
NS: Flashing green
Waiting to connect to
DeviceNet communica-
tions.
Check the following items and restart
the Controller.
Are lengths of cables (trunk and
branch lines) correct?
Are cables short-circuited, broken,
or loose?
Are cables wired correctly?
Is terminating resistance connected
to both ends of the trunk line only?
Is noise interference excessive?
Is the power to the master ON?
The Digital Controller is
faulty.
Repairs are required. Contact your
nearest OMRON representative.
MS: ON green
NS: ON red
The DeviceNet is in Bus
OFF status.
Check the following items and restart
the Controller.
Are lengths of cables (trunk and
branch lines) correct?
Are cables short-circuited, broken,
or loose?
Is terminating resistance connected
to both ends of the trunk line only?
Is noise interference excessive?
Node addresses dupli-
cated.
Reset node addresses correctly.
The Controller is faulty. Repairs are required. Contact your
nearest OMRON representative.
MS: ON green
NS: Flashing red
A communications time-
out has occurred.
Check the following items and restart
the Controller.
Are lengths of cables (trunk and
branch lines) correct?
Are cables short-circuited, broken,
or loose?
Is terminating resistance connected
to both ends of the trunk line only?
Is noise interference excessive?
The Digital Controller is
faulty.
Repairs are required. Contact your
nearest OMRON representative.