DeviceNet Communications Cables Wiring Section 3-3
Parts, Installa-
tion, and Wiring
The colors correspond to the signal lines as follows:
• We recommend the following crimp terminals (for Thin Cables) 
Power Lines: Phoenix Contact AI-series Crimp Terminals AI-0.5-6WH
(product code 3200687)
Signal Lines: Phoenix Contact AI-series Crimp Terminals AI-0.25-6BU
(product code 3201291)
The following crimp tool is also available.
Phoenix Contact ZA3 Crimp Tool
3-3-2 Attaching the DeviceNet Communications Unit Connector
Align the DeviceNet Communications Unit connector with the cable connec-
tor, and insert the cable connector fully into the DeviceNet Communications
Unit connector.
Tighten the set screws to a torque between 0.25 and 0.3 N·m to secure the
connector.
E5AR
Color Signal
Red Power line, positive voltage (+V)
White Communications line, high (CAN high)
--- Shield
Blue Communications line, low (CAN low)
Black Communications cable, negative voltage (−V)
 
Black (−V)
Blue (CAN low)
Shield
White (CAN high)
Red (+V)
 
Crimp terminal
Line
Insert the line and crim