B-5
Mounted Objects Appendix B
Appendix B
Note Produced Connection Paths
IN Area 1: 20_04_24_64_30_03
IN Area 2: 20_04_24_65_30_03
Object
instance 4
Section Information Maximum number of instances
Instance type COS Cyclic 1
Production
trigger
Cyclic
Transport type Server
Transport
class
2
Attribute ID Contents Get (read) Set (write) Value
1 State Yes No
2 Instance type Yes No 01 (hexadecimal)
3 Transport class trigger Yes No 12 (hexadecimal)
4 Produced connection ID Yes No
5 Consumed connection ID Yes No
6 Initial comm. characteristics Yes No 01 (hexadecimal)
7 Produced connection size Yes No
8 Consumed connection size Yes No 0800 (hexadecimal)
9 Expected packet rate Yes Yes
12 Watchdog time-out action Yes No 00 (hexadecimal)
13 Produced connection path
length
Yes No 06 (hexadecimal)
14 Produced connection path Yes No See note.
15 Consumed connection path
length
Yes No 04 (hexadecimal)
16 Consumed connection path Yes No 202B2401
17 Production inhibit time Yes Yes 0000 (hexadecimal)
Service DeviceNet service Parameter option
05 Reset None
0E Get_Attribute_Single None
10 Set_Attribute_Single None