3 Communications Data for CompoWay/F
3 - 20
E5C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
C3 (83) 00AC Download Setting
4
H'0000001E to H'000000B3 (30 to 179) Communi
cations
setting
C3 (83) 00AD Download Setting
5
H'0000001E to H'000000B3 (30 to 179)
C3 (83) 00AE Download Setting
6
H'0000001E to H'000000B3 (30 to 179)
C3 (83) 00AF Download Setting
7
H'0000001E to H'000000B3 (30 to 179)
C3 (83) 00B0 Download Setting
8
H'0000001E to H'000000B3 (30 to 179)
C3 (83) 00B1 Download Setting
9
H'0000001E to H'000000B3 (30 to 179)
C3 (83) 00B2 Download Setting
10
H'0000001E to H'000000B3 (30 to 179)
C3 (83) 00B3 Download Setting
11
H'0000001E to H'000000B3 (30 to 179)
C3 (83) 00B4 Download Setting
12
H'0000001E to H'000000B3 (30 to 179)
C3 (83) 00B5 Download Setting
13
H'0000001E to H'000000B3 (30 to 179)
C3 (83) 00B8 LCT Cooling
Output Minimum
ON Time
H'00000001 to H'0000000A (0.1 to 1.0) Advanced
function
setting
C3 (83) 00B9 Program Time Unit H'00000000 (0): Hours, minutes
H'00000001 (1): Minutes, seconds
Initial
setting
C3 (83) 00BA Step Time/Rate of
Rise Programming
H'00000000 (0): Step time programming
H'00000001 (1): Rate of rise programming
C3 (83) 00BB Time Unit of Ramp
Rate
H'00000000 (0): Minutes
H'00000001 (1): Hours
C3 (83) 00BC Reset Operation H'00000000 (0): Stop control
H'00000001 (1): Fixed SP operation
C3 (83) 00BD Startup Operation H'00000000 (0): Continue control at final SP
H'00000001 (1): RESET
H'00000002 (2): RUN
H'00000003 (3): Manual
*1
C3 (83) 00BE Operation End
Operation
H'00000000 (0): RESET
H'00000001 (1): Continue control at final SP
H'00000002 (2): Fixed SP mode
*2
C3 (83) 00BF PV Start H'00000000 (0): SP start
H'00000001 (1): PV Start
C3 (83) 00C0 Program End ON
Time
H'00000000 to H'00000064 (0.0 to 10.0)
H'FFFFFFFF (ON)
Advanced
function
setting
C3 (83) 00C1 Standby Time Unit H'00000000 (0): Hours, minutes
H'00000001 (1): Days, hours
C3 (83) 00C4 Valve Completely
Closed Position
H'00000000 to H'0000270F (0 to 9999) Initial
setting
C3 (83) 00C5 Valve Completely
Open Position
H'00000000 to H'0000270F (0 to 9999)
C3 (83) 00C6 Potentiometer
Specification
Setting
H'00000000 to H'00000005 (0 to 5)
C3 (83) 00C8 All PID AT Upper
Limit SP
SP lower limit to SP upper limit
Variable
type