SECTION 2 CompoWay/F Communications Procedures
2-16
Error Occurred
(3) Operation Commands and Precautions
● Communications Writing
Set the “communications writing” parameter to “ON: enabled” or “OFF:
disabled” with the related information setting. The setting can be
accepted in both setup area 0 and setup area 1.
● RUN/STOP
Set control to “run” or “stop” with the related information setting. The
setting can be accepted in both setup area 0 and setup area 1.
● Multi-SP
Set four set points beforehand in the adjustment level so that you can
switch to a desired set point. The setting can be accepted in both setup
area 0 and setup area 1.
● AT Execute/Cancel
Set AT (auto-tuning) to “execute” or “cancel” with the related information
setting. This command can be accepted in setup area 0 only. An
“operation error” will be generated in the following instances:
• When the “run/stop” parameter is set to “stop”
• When the command is executed in “setup area 1”
• When ON/OFF control is being used
● Write Mode
Set either the backup mode or RAM write mode with the related infor-
mation setting. The setting can be accepted in both setup area 0 and
setup area 1.
Response code Error name Cause
1001 Command too long The command is too long.
1002 Command too short The command is too short.
1100 Parameter error Command code and related
information are wrong.
2203 Operation error • The “communications writ-
ing” parameter is set to
“OFF” (disabled). The com-
mand is received regardless
of the “communications writ-
ing” parameter setting (ON/
OFF).
• Processing could not be per-
formed. For details, see (3)
Operation Commands and
Precautions below.
• EEPROM error