28
Starting frequency 10D1h b082 5 ~ 99 0.1[Hz] 1355h b082
1~999 (In the high-frequency
mode︓~10000)
0.01[Hz]
Carrier frequency 10D2h b083 20 ~ 120 0.1[kHz] 1356h b083 20~150 (100) 0.1[kHz]
Initialization selection 10D3h b084
00: Clears the trip monitor
01: Initializes data
02: Clears the trip monitor and
initializes
data
- 1357h b084
00: Initialization disabled
01: Clearing fault monitor
02: Initialize data
03: Clear fault monitor + Initialize
data
04: Clear fault monitor + Initialize
data + Clear DriveProgramming
-
Initialization parameter
selection
10D4h b085
00: Fixed
Do not change.
- 1358h b085 Do not change the default 00. -
Frequency conversion
10D5h b086 1 ~ 999 0.1 1359h b086 1~9999 0.01
STOP key selection 10D6h b087
00: Enabled
01: Disabled
- 135Ah b087
00: Enabled
01: Disabled
02: Only RESET enabled
-
Free-run stop selection 10D7h b088
00: 0 Hz start
01: Frequency pull-in restart
- 135Bh b088
00: 0-Hz restart
01: Frequency matching restart
02: Frequency pull-in restart
-
Stop selection 10DAh b091
00: Deceleration→Stop
01: Free-run stop
- 135Eh b091
00: Deceleration stop
01: Free-run stop
-
Cooling fan control 10DBh b092
00: Always ON
01: ON during RUN
02: Depends on the fin temperature
- 135Fh b092
00: Always enabled
01: Enabled only during operation
(including 5 minutes after power
on/stop)
02: Dependent on cooling fin
temperature
-
Overvoltage protection
function selection during
deceleration
1176h b133
00: Disabled
01: Enabled - 1385h b130
00: Disabled
01: DC voltage kept constant
02: Acceleration enabled
-
Overvoltage protection level
setting during deceleration
1177h b134
200-V class: 330. to 395.
400-V class: 660. to 790.
1[V] 1386h b131
200-V class: 330 to 395
400-V class: 660 to 790
1[V]
Overcurrent suppression
function
10F7h b140
00: Disabled
01: Enabled
- 131Ch b027
00: Disabled
01: Enabled
02: Enabled (at reduced voltage
startup)
-
Automatic carrier reduction 10F8h b150
00: Disabled
01: Enabled
- 135Ch b089
00: Disabled
01: Enabled (dependent on current)
02: Enabled (dependent on cooling
fin temperature)
-