Sends data to a node on the network.
Instruction Name
FB/
FUN
Graphic expression ST expression
Send
Send to Net-
work
FB
Send
Send
_instance
Execute
DstNetAdr
Done
CommPort
SrcDat
SendSize
DstCh
Option
Error
ErrorID
DstArea
Busy
ErrorIDEx
Send_instance(Execute, DstNe-
tAdr, CommPort, SrcDat, Send-
Size, DstArea, DstCh, Option,
Done, Busy
, Error, ErrorID, ErrorI-
DEx);
Variable
Name
Input/
output
Contents Valid range Unit
Initial
value
DstNetAdr
Network address at
send destination
Input
Specifies the network
address and node ad-
dress at send destina-
tion
--- --- ---
CommPort
Designation of port at
send destination
Specifies the serial
port at send destina-
tion
_NONE --- _NONE
SrcDat[] ar-
ray
First element of array
at send destination
Beginning of data (ar-
ray) to be sent
16#0000 to
16#FFFF
---
*1
SendSize Number of send words
Specifies the number
of words in the send
data
0 to Max. data
length
*2
Word 1
DstArea
Area at send destina-
tion
Specifies the area type
at send destination
_CIO
_WR
_HR
_TIMER
_COUNTER
_DM
_EM0
_EM18
--- _DM
DstCh CH at send destination
Specifies the first ch at
send destination
0 to 32,767 ch 0
Option Response
Specifies response
monitoring and resend-
ing
--- --- ---
*1. If you omit an input parameter, the default value is not applied. A building error will occur.
*2. This may vary depending on the network type.
3 Client Function
3-4
NX-series CPU Unit FINS Function User's Manual (W596)

Other manuals for Omron NX1 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NX1 Series and is the answer not in the manual?

Omron NX1 Series Specifications

General IconGeneral
BrandOmron
ModelNX1 Series
CategoryController
LanguageEnglish

Related product manuals