Variable name Meaning Function Data type
Range of
values
Reference
_EIP2_RegTarget-
Sta[255]
CIP Communica-
tions2 Registered
T
arget Node Informa-
tion
Gives a list of nodes for which built-in
EtherNet/IP connections are registered
for CIP communications 2.
This variable is valid only when the built-
in EtherNet/IP port is the originator.
Array[x] is TRUE:
The connection to the node with a target
node ID of x is registered.
Array[x] is FALSE:
The connection to the node with a target
node ID of x is not registered.
Note You can use this system-de-
fined variable only for the
NX701 CPU Units and NX102
CPU Units.
ARRAY
[0..255] OF
BOOL
TRUE or
FALSE
page 3-54
_EIP_EstbTarget-
Sta[255]
Normal Target Node
Information
NX-series CPU Units: Gives a list of no-
des that have normally established built-
in EtherNet/IP connections for CIP com-
munications 1.
Array[x] is TRUE:
The connection to the node with a target
node ID of x was established normally
.
Array[x] is FALSE:
The connection to the node with a target
node ID of x was not established, or an
error occurred.
NJ-series CPU Units: Gives a list of no-
des that have normally established built-
in EtherNet/IP connections.
Array[x] is TRUE:
The connection to the node with a target
node ID of x was established normally.
Array[x] is FALSE:
The connection to the node with a target
node ID of x was not established, or an
error occurred.
ARRAY
[0..255] OF
BOOL
TRUE or
FALSE
page 3-55
_EIP1_EstbTarget-
Sta[255]
CIP Communica-
tions1 Normal T
arget
Node Information
Gives a list of nodes that have normally
established built-in EtherNet/IP connec-
tions for CIP communications 1.
Array[x] is TRUE:
The connection to the node with a target
node ID of x was established normally.
Array[x] is FALSE:
The connection to the node with a target
node ID of x was not established, or an
error occurred.
Note You can use this system-de-
fined variable only for NX-ser-
ies CPU Units.
ARRAY
[0..255] OF
BOOL
TRUE or
FALSE
page 3-55
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-25
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
3-2 System-defined Variables
3