90-/100-/240-W models with PFC (S82K-P
jjj
24 models)
Item
Single output
90 W 100 W 240 W
Efficiency (typical)
60% to 80% (Varies depending on specifications.)
Input
Voltage
100 V (85 to 132 V AC)/200 V (170 to 264 VAC)
Selectable
100 to 230 V (85 to 253 VAC)
Frequency
50/60Hz(47to63Hz)
Current
100-V input
2.5 A max. 4Amax.
see
note 1)
200-V input
1.0 A max. 2Amax.
Power
100-V input
--- 0.95 min.
factor
200-V input
0.7 min. 0.95 min.
Leak-
age cur-
100-V input
0.5 mA max.
rent
(see
note 1)
200-V input
1mAmax.
Inrush
current
100-V input
25 A max.
(see
note 1)
200-V input
50 A max.
Noise filter
Yes
Output
(see note
Voltage adjustment
range
!
10% (V.ADJ)
2)
Ripple (see note 1)
2% (p-p) max.
Input variation
influence
0.5% max. (at 85 to 132 VAC/170 to 264 V AC input,
100% load)
0.5% max. (at 85 to 253 VAC input,
100% load)
Load va riation
influence
1.5% max. (0 to 100% load) 1.5% max. (10 to 100% load)
Temperature variation
0.05%/
"
Cmax.
Start up time
200 ms max. 1,000 ms max.
Hold time (see note 1)
20 ms min.
Addition-
al func-
tion
Overload protection
101% to 1 11% of rated
load current, inverted L
drop, automatic reset (see
note 3)
105% to 160% of rated load current, inverted L drop, automatic
reset
Overvoltage
protection
No
Under voltage alarm
indicator
Yes (color: red) No
Under voltage alarm
output
Yes No
Parallel operation
Impossible Possible (2 units max.) (see note 4)
Note:
1. Defined with a 100% load and the rated input voltage (100 or 200 VAC)
2. The output specification is defined at the power supply output terminals.
3. When the ambient temperature exceeds 25
"
C, the protection function will operate at a current of 92% to 1 11% of the rated load
current.
4. Parallel operation is set with the Parallel/Single Operation Selector Switch.