04 Commissioning
04.5 Important parameters
The parameters for operating a SPINOGY spindle can be taken from the corresponding parameter list (available
from SPINOGY). This includes a useful selection of the respective parameters. In case one of the parameters
should be programmed differently, the following table lists the most important parameters with the respective
option possibility. In addition, these parameters must be programmed before starting the spindle for the first time,
if an unprogrammed frequency converter has been purchased from SPINOGY.
Base parameters
Func. code
Name
Description
A001
Frequency reference selection
Eight options; select codes:
00 ... VR (Digital Operator)
01 ...Terminal
02 ...Operator (F001)
03 ...ModBus (RS485)
04 ...Option
06 ...Pulse train frequency
07...EzSQ (Drive programming)
10...Math (operator function result)
A002
Run command selection
Five options; select codes:
01 ...Terminal
02 ...Operator (F001)
03 ...ModBus (RS485)
04 ...Option
A003
Base frequency
See type plate spindle
A004
Maximum frequency
B012
Rated current
F001
Output frequency setting/monitor
Standard default target frequency that determines
constant motor speed, range is 0.0 / start
frequency to maximum frequency (A004)
F002
Acceleration time
0,00 bis 3600,00
F003
Deceleration time
H004
Motor pole number selection
See type plate spindle
Parameters for braking resistor
The following parameters must be set when using an external braking resistor. The parameters can be taken
from the parameter list when using a SPINOGY braking resistor or must be set according to the specifications
of the braking resistor used.
Func. code
Name
Description
B090
Usage rate of regenerative
braking function
Selects the rate of use (in %) of the regenerative
braking resistor per 100 sec. intervals, range is
0.0 to 10.0%.
0%: Function disabled
B095
Regenerative braking function
operation selection
Three option codes:
00 OFF (Disabled)
01 RUN-ON (Enabled) (Disabled during stop)
02 Alws-ON (Enabled during stop)
B097
BRD resistor
Ohmic value of the braking resistor connected to
the drive 100.0 to 600.0 Ω

Related product manuals