22
06 Troubleshooting
E40
Operator connection
When the connection between inverter
and operator keypad failed, inverter trips and
displays the error code.
E41
Modbus communication
error
When “trip” is selected (C076=00) as a
behavior in case of communication error,
inverter trips when timeout happens.
E43
Drive Programming invalid
instruction
The program stored in inverter memory has
been destroyed, or the PRG terminal was
turned on without a program downloaded to the
inverter.
E44
Drive Programming
nesting count error
Subroutines, if-statement, or for-next loop are
nested in more than eight layers
E45
Drive Programming
instruction error
Inverter found the command which cannot be
executed.
E50 bis E59
Drive Programming user
trip (0 to 9)
When user -defined trip happens, inverter trips
and displays the error code.
E60 bis E69
Option errors (error in
connected
option board, the
meanings change upon
the connected option).
These errors are reserved for the option board.
Each option board can show the errors for a different
meaning .. To check the specific meaning,
please refer to the corresponding option
board user manual and documentation.
E80
Encoder disconnection
If the encoder wiring is disconnected, an
encoder connection error is detected, the
encoder fails, or an encoder that does not
support line driver output is used, the inverter
will shut off its output and display the error
code shown on the right.
E81
Excessive speed
If the motor speed rises to “maximum frequency
(A004) x overspeed error detection level (P026)”
or more, the inverter will shut off its output and
display the error code shown on the right.
E83
Positioning range error
If current position exceeds the position range
specification (P072-P073), the inverter will shut
off its output and display the error code.
It is recommended not to acknowledge an error until the cause of the error has been found, to avoid greater
damage. If the cause is not found, please contact SPINOGY.
An error can be acknowledged by pressing the STOP/RESET key, and the frequency inverter can be reset to the
initial state.