SRT1-jD08S
SRT1-jD08S
52
Indicators
Indicator Name Display Color Meaning
PWR Power supply Lit Green
The communications power supply is ON.
Not lit
The communications power supply is OFF
.
COMM Communication Lit Yellow
Normal communications
Not lit
A communications error has occurred or the Unit is in standby status.
ERR
Communication
Lit Red
A communications error has occurred.
error
Not lit
Normal communications or the Unit is in standby status.
0 to 3
Input Lit Yellow
The corresponding input is ON.
0 to 7 (8 inputs)
Not lit
The corresponding input is OFF or the Unit is in standby status.
0 to 3
Output Lit Yellow
The corresponding output is ON.
(4 inputs/outputs)
Not lit
The corresponding output is OFF or the Unit is in standby status.
Switch Setting
All
pins are factory-set to OFF
.
Hold/Clear
outputs for
communications error
Node number
settings
Reserved (OFF)
Pin 5 (Reserved)
Always
set pin 5 to OFF
.
Output HOLD/CLEAR Mode (SRT-ND16S)
HOLD Function
OFF Output
status is cleared when a
communications error occurs.
ON
Output status is maintained when a
communications error occurs.
Node Number Settings
Node
number
1 2 4 8
0 OFF OFF OFF OFF
1 ON OFF OFF OFF
2 OFF ON OFF OFF
3 ON ON OFF OFF
4 OFF OFF ON OFF
5 ON OFF ON OFF
6 OFF ON ON OFF
7 ON ON ON OFF
8 OFF OFF OFF ON
9 ON OFF OFF ON
10 OFF ON OFF ON
11 ON ON OFF ON
12 OFF OFF ON ON
13 ON OFF ON ON
14 OFF ON ON ON
15 ON ON ON ON