Loading...
SRT1-jD08S
SRT1-jD08S
53
SRT1-OD08S
DIP Switch
Mounting Screw Holes
Used when screwing the Unit to a control panel.
CompoBus/S Indicators
Indicate the operating status of the Slave and the status of communications.
Output Indicators
Indicate the output sta
-
tus of each channel.
Communications T
erminals
Communications Power
Supply T
erminals
Connect the communica
-
tions cable.
DIN Track
Mounting Hook
Used when mounting the Unit
to a DIN track.
Output Connectors
Connect the cables from
the output device.
Switch Setting
All
pins are factory-set to OFF
.
Hold/Clear
outputs for
communications error
Node number
settings
Reserved (OFF)
Pin 5 (Reserved)
Always
set pin 5 to OFF
.
Output HOLD/CLEAR Mode (SRT-ND16S)
HOLD Function
OFF Output
status is cleared when a
communications error occurs.
ON
Output status is maintained when a
communications error occurs.
Node Number Settings
Node
number
4 3 2 1
0 OFF OFF OFF OFF
1 OFF OFF OFF ON
2 OFF OFF ON OFF
3 OFF OFF ON ON
4 OFF ON OFF OFF
5 OFF ON OFF ON
6 OFF ON ON OFF
7 OFF ON ON ON
8 ON OFF OFF OFF
9 ON OFF OFF ON
10 ON OFF ON OFF
11 ON OFF ON ON
12 ON ON OFF OFF
13 ON ON OFF ON
14 ON ON ON OFF
15 ON ON ON ON