1-10
1-2-2 Standard Connections
DC reactor
(optional)
Noise Filter
Single-phase 100 V AC
Forward/Stop
Multi-function input 1 (Reserve/Stop)
Multi-function input 2 (S3) (Fault Reset)
Multi-function input 3 (S4) (External fault
Normally open)
Multi-function input 4 (S5) (Multi-step speed
reference 1)
Sequence input common
Frequency reference power
supply 20 mA at +12 V
FREQ
adjuster
Frequency reference input
Frequency reference common
Multi-function contact output
NO
NC
Common
Analog monitor output
Analog monitor output common
(2 k, 1/4 W min.)
3-phase 200 V AC
Note 1. The braking resistor cannot be connected because no braking transistor is incorporated.
Note 2. A DC Reactor can be connected in series between the R input and L1 terminal or between the
S input and L2 terminal to use it as an AC reactor.
D DC Reactor Wiring Example
Noise Filter
DC Reactor
Single-phase 100 V AC
Applicable Noise Filters
Inverter Applicable Filter Specifications
3G3JV-A1001
3G3JV-PRS1010J
(f ih 01kW 02kW)
10 A at 250 V AC, single-phase
3G3JV-A1002
(for either 0.1 kW or 0.2 kW)
,gp
Applicable DC Reactors
Inverter Applicable Reactor Specifications
3G3JV-A1001 3G3HV-PUZDAB5.4A8MH 5.4 A, 8 mH
3G3JV-A1002 3G3HV-PUZDAB18A3MH 18 A, 3 mH
Design Chapter 1