3-16
Param-
eter
No.
(Regis-
ter No.
(Hex))
MemoChanges
during
opera-
tion
Default
setting
Set-
ting
range
DescriptionName
n62
(013E)
UP/DOWN
command
frequency
memory
Used to store the adjusted frequency refer-
ence with the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or
more.
Used to store the adjusted frequency refer-
ence with the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or
more.
Used to store the adjusted frequency refer-
ence with the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or
more.
0, 1 0 No
n63
(013F)
Torque
compensa-
tion gain
Used to set the gain of the torque compensa-
tion function.
The default setting does not need any
changes in normal operation.
0.0 to
2.5
1.0 Yes
n64
(0140)
Motor
rated slip
Used to set the rated slip value of the motor in
use.
Note Used as the constant of the slip com-
pensation function.
0.0 to
20.0
Varies
with the
capac-
ity.
Yes
n65
(0141)
Motor no-
load cur-
rent
Used to set the no-load current of the motor in
use based on the rated motor current as
100%.
Note Used as the constant of the slip com-
pensation function.
0 to
99
Varies
with the
capac-
ity.
No
n66
(0142)
Slip com-
pensation
gain
Used to set the gain of the slip compensation
function.
Note The slip compensation function is dis-
abled with n66 set to 0.0.
0.0 to
2.5
0.0 Yes
n67
(0143)
Slip com-
pensation
time
constant
Used for the response speed of the slip com-
pensation function.
Note The default setting does not need any
changes in normal operation.
0.0 to
25.5
2.0 No