EasyManua.ls Logo

Omron SYSDRIVE 3G3SV - 2-9 Function;Constant List

Omron SYSDRIVE 3G3SV
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
/
2-9 Function/Constant List
First Functions (Constant Nos. 0 to 19)
Function No. Name Description Initial
setting
User
set
values
See
page
Password
setting
0 Password 0: Password (No. 00) setting/reading and
first function (constant Nos. 1 to 19)
reading possible
1 43
Constant
write-in
prohibit
1: First function (constant Nos. 0 to 19) set-
ting/reading possible
2: First and second function (constant Nos.
0 to 29) setting/reading possible
Constant
group se-
lection
3: First, second and third function (constant
Nos. 0 to 59) setting/reading possible
Fault con-
tents clear
6: Fault record clear
Constant
initializa-
tion
8: Initialize (multifunction terminal: initial
value setting)
9: Initialize (3-wire sequence)
Operation
method
selection
1 Run signal
selection 1
1st digit = 0: Main frequency reference-ex-
ternal terminals 11 and 13 in-
puts
1: Main frequency reference-op-
erator Fxxxx
2nd digit = 0: Run by external terminal run
command
1: Run by operator run com-
mand
0000 44
Stopping
method
selection
3rd digit = 0: Deceleration to a stop
1: Coasting to a stop
Output
voltage li-
mitter
Output volt-
age limitter
4th digit = 0: With output voltage limitter
1: Without output voltage limitter
56
V/f char-
acteristic
setting
2 Maximum
frequency
Setting unit: 0.1 Hz, setting range: 50.0 to
400.0 Hz
60.0 Hz 44
3 Maximum
voltage
Setting unit: 0.1 V, setting range: 0.1 to
255.0 V
200.0 V 44
4 Maximum
voltage fre-
quency
(base fre-
quency)
Setting unit: 0.1 Hz, setting range: 0.1 to
400.0 Hz
60.0 Hz 44
5 Intermediate
output fre-
quency
Setting unit: 0.1 Hz, setting range: 0.1 to
400.0 Hz
1.5 Hz 44
6 Intermediate
output fre-
quency volt-
age
Setting unit: 0.1 V, setting range: 0.1 to
255.0 V
12.0 V 44
 "
Section 2-9

Related product manuals