Function See
Page
User
set
values
Initial
setting
DescriptionNameNo.
Overtorque de-
tection
37 Overtorque
detection
function se-
lection
1st digit = 0: Overtorque detection not
provided
= 1: Overtorque detection pro-
vided
0000 50
2nd digit = 0: Detected only during
speed coincidence
= 1: Detected during running
3rd digit = 0: Operation continued after
overtorque detection
= 1: Output shut-off at overtor-
que detection
4th digit: Not used
38 Overtorque
detection
level
Setting unit: 1%, setting range: 30% to
200%
160%
39 Overtorque
detection
time
Setting unit: 0.1 s, setting range: 0.1 to
10.0 s
0.1 s
Carrier fre-
quency adjust-
ment
40 Carrier fre-
quency
Setting unit: 2.5 kHz, setting range: 1 to
6(2.5to15kHz)
4
(10 kHz)
51
Multi-step
speed frequen-
f
41 Frequency
reference 5
Setting unit: 0.1 Hz, setting range: 0.0 to
400.0 Hz
0.0 Hz 45
q
cy reference
(see note)
42 Frequency
reference 6
Setting unit: 0.1 Hz, setting range: 0.0 to
400.0 Hz
0.0 Hz
43 Frequency
reference 7
Setting unit: 0.1 Hz, setting range: 0.0 to
400.0 Hz
0.0 Hz
44 Frequency
reference 8
Setting unit: 0.1 Hz, setting range: 0.0 to
400.0 Hz
0.0 Hz
Analog monitor
scale calibra-
tion
45 Analog mon-
itor gain
Setting unit: 0.01, setting range: 0.01 to
2.00
1.00 50
Momentary
power loss
protection
46 1st digit = 0: Operation stopped by mo-
mentary power loss detec-
tion
= 1: Operation continues after
momentary power loss
0000 43
Auto reset/re-
start operation
47 No.ofauto
restart at-
tempts
0 43
Fault trace 48 Fault record The latest fault is number of auto restart
attempt: 0 to 10 (setting disabled).
---
 "
Section 2-9

Related product manuals