7 Programming Functions ZEN Programmable Logic Module
OMRON ELECTRONICS, S.A. Page 28
7.4.1. Settings in the Ladder Program
Calendar timer inputs are written in the Edit Screen. Settings are carried out
in the parameter settings screen.
No. of Calendar Timer *0 to *7
7.4.2. Settings in the Parameter Settings Screen
Start date Jan 1 to Dec 31
Stop date
(see note)
Jan 1 to Dec 31
A The parameters can be
modified and monitored
Monitoring
enabled/disabled
D The parameters cannot be
modified or monitored
Setup and operation Example Operation
When the start date is
before the stop date
ON:04/01
OFF: 09/01
Operates between 1 April and 31 August
(see note)
When the start date is
after the stop date
ON: 12/26
OFF: 01/07
Operates between 26 December and 6 January
of the following year
Start and stop date
When the start and stop
dates are the same
ON: 07/26
OFF: 07/26
Operates regardless of the set date
Note.
To stop operation on 31 August, the following days date (1 September) should
be set as the stop date.
Calendar timer address