9 Accessories ZEN Programmable Logic Module
OMRON ELECTRONICS, S.A. Page 40
Menu Operation
Save Transfers the CPU program to the Memory
Cassette. Any program already in the cassette
will be overwritten.
Load Transfers the Memory Cassette program to
the CPU. Any program already in the CPU will
be overwritten.
Erase Clears the program from the Memory
Cassette.
Note.
1. Program transfer includes the ladder program, parameters and all data
settings. Normal and holding timers, counters and holding bits present
values cannot be transferred.
2. Only error-free programs can be transferred. The program will not be
transferred if it contains any type of error.
3. The memory cassette allows 100,000 writes.
9.3. Connecting the ZEN Support Software
The Software can be used either for ZEN programming or for monitoring. For
further information about the functions or operations, see the ‘ZEN-SOFT01
ZEN Support Software Operation Manual’ (W386).
Conditions
Operating System Windows 95, 98, ME, 2000,
NT 4.0 Service Pack 3
CPU Pentium 133 MHz or higher
Memory 64 Mbytes min.
Hard disc 40 Mbytes free disc space min.
CD-ROM drive Required
Communications Serial port
Keyboard and
mouse
Required
Monitor 800x600 dots (SVGA) min. 256
colors min.