Item to verify
Serial Number: Serial Number: Serial Number: Serial Number:
1. What is the Pipe ID? ID = ID = ID = ID =
2. Calculate the Upstream/
Downstream straight-pipe
requirements
UP =
DN =
UP =
DN =
UP =
DN =
UP =
DN =
3. a. Is the flow indicator
pointed in direction of flow?
b. Must the housing be
rotated for easy viewing?
Y / N
Y / N
Y / N
Y / N
Y / N
Y / N
Y / N
Y / N
4. Is the probe depth setting
correct?
Y / N Y / N Y / N Y / N
5. Have you rotated the display
for easier viewing?
Y / N Y / N Y / N Y / N
6. Verify proper power wiring
setup
7. Verify proper output wiring
setup
After powering on your meter, check items A - D below by accessing the meter settings either through the
front panel of the meter's display or by using the F-5000 View software tool.
A. Which flow units have been
set in meter? (SCFH, KG/H,
etc..)
B. Correct values for reference
temperature and pressure?
Y / N Y / N Y / N Y / N
C. Confirm the pipe ID listed
above same as "Pipe_id="
D. Verify the 4mA and 20mA
meter settings
4mA =
20mA =
4mA =
20mA =
4mA =
20mA =
4mA =
20mA =
Your Notes:
Before powering on your meter, use this worksheet to record your notes.
If you are experiencing any problems after completing this procedure, please call the ONICON Service
Department at 727-447-6140 to review this information.
Installation -
Model F-5500
Flow Meter
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com
F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page 16
Model F-5500
DISCLAIMERINTRODUCTION
Introduction: Quick Start Guide
Installation: General