EasyManua.ls Logo

Onicon F-5500 - HART Wiring; HART 4-20 mA Output Wiring: Customer-Supplied Power Source

Onicon F-5500
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
i
Fig. 3.8-3.9, IMPORTANT NOTES:
When using a 12 volt power supply, the load resistor on the 4-20mA output must be
125 ohms or less to operate properly.
When using 24 volt power, the load resistor is typically 250 ohms. A 250 ohm
resistor in the 4-20mA circuit will result in a 1 to 5 volt signal to the PLC or DCS.
When using a 24 volt power supply, the load resistor on the 4-20mA output must be
600 ohms or less.
Some PLC and DCS equipment have built in load resistors, please refer to the
technical manuals of such equipment.
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com
F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page 36
Model F-5500
WIRING
Wiring: HART
HART Wiring
i
Fig. 3.7, IMPORTANT NOTE:
The load resistor on the ONICON Flow Meter 4-20mA signal is typically 250 ohms
and is located in or at the customer's PLC or DCS. A 250 ohm resistor in the 4-20mA
line will result in a 1 to 5VDC signal to the PLC or DCS. Some PLC/DCS equipment
has the load resistor built in to the unit; please refer to the PLC/DCS technical manual.
Do not exceed a 600 ohm load on the ONICON Flow Meter 4-20mA signal.
(
-
) (+) (
-
) (+) (
-
) (+)
Power
12-28VDC
4-20mA Pulse
/Alarm
!
+12 to 28VDC
12 to 28VDC Return
*(see important note below)
F-5500
Customer PLC or DCS
HART
Modem
HART Wiring
The HART connections are accessed by removing the cover of the F-5500 enclosure.
HART 4-20mA Output Wiring: Customer-Supplied Power Source
The 4-20mA current loop and HART modem connections are made as shown in the
diagram below.
Fig. 3.7: HART Wiring
, Customer-Supplied Power Source