Power
12-28VDC
4-20mA Pulse
/Alarm
!
+12 to 28VDC
12 to 28VDC Return
+
-
F-5500
Customer PLC or DCS
4-20mA Flow Rate or Temperature
250 ohms typical with 24VDC Power
125 ohms or less for 12VDC Power
*(see notes below)
i
4-20mA Output Wiring: Customer-Supplied Power Source
Bring the 4-20mA wiring in through either conduit hub. Connect 4-20mA wiring as
shown in the diagram below.
Fig. 3.2: 4-20mA Output Wiring for Customer-Supplied Power Source
IMPORTANT NOTES:
• When using a 12 volt power supply, the load resistor on the 4-20mA
output must be 125 ohms or less to operate properly.
• When using 24 volt power, the load resistor is typically 250 ohms. A 250
ohm resistor in the 4-20mA circuit will result in a 1 to 5 volt signal to the
PLC or DCS.
• When using a 24 volt power supply, the load resistor on the 4-20mA
output must be 600 ohms or less.
• Some PLC and DCS equipment have built in load resistors, please refer to
the technical manuals of such equipment.