Power
12-28VDC
4-20mA Pulse
/Alarm
!
+12 to 28VDC
12 to 28VDC Return
+
-
F-5500
Customer PLC or DCS
4-20mA Flow Rate or Temperature
250 ohms typical with 24VDC Power
125 ohms or less for 12VDC Power
*(see notes below)
i
4-20mA Output Wiring: Customer-Supplied Power Source
Bring the 4-20mA wiring in through either conduit hub. Connect 4-20mA wiring as
shown in the diagram below.
Fig. 3.2: 4-20mA Output Wiring for Customer-Supplied Power Source
IMPORTANT NOTES:
When using a 12 volt power supply, the load resistor on the 4-20mA
output must be 125 ohms or less to operate properly.
When using 24 volt power, the load resistor is typically 250 ohms. A 250
ohm resistor in the 4-20mA circuit will result in a 1 to 5 volt signal to the
PLC or DCS.
When using a 24 volt power supply, the load resistor on the 4-20mA
output must be 600 ohms or less.
Some PLC and DCS equipment have built in load resistors, please refer to
the technical manuals of such equipment.
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com
F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page 31
Model F-5500
WIRING
Wiring: Signal Wiring
4-20mA Loop
Power Provided
by Customer
(Recommended)