IMPORTANT NOTE:
In order to use the RS485 feature on the Model F-5500, this feature
must be chosen when the meter is ordered from the factory.
Modbus RTU and BACnet MS/TP are not available with meters
ordered with the Pulse/Alarm option.
W1 jumper will be shipped in the open or unterminated position. It
should be in the terminated position on the last meter in the series.
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com
F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page 35
Model F-5500
WIRING
(
-
) (+)
Power
12-28VDC
4-20mA(
-
)
!
4-20mA(+)
Common
Tx/Rx(
-
)
Tx/Rx(+)
Tx/Rx(+)
Termination Resistor Jumper W1
Tx/Rx(
-
)
Communication Common
Termination Resistor Jumper (detail)
Terminated
No Termination (Open)
RS485 Wiring for RS485 Modbus RTU or BACnet MS/TP
Wiring connections are made as shown in the diagram below for Modbus or BACnet
communication.
Termination Resistor
Connect a termination resistor across the receive/transmit signals of the last device on
the communication line. To connect the 120 ohm termination resistor on the F-5500,
set jumper W1 to the TERM position.
Disconnect the termination resistor on all other external RS485 devices. The
termination resistor of the F-5500 is disconnected by setting jumper W1 to the OPEN
position.
Fig. 3.6: RS485 Wiring
Wiring: RS485 Modbus RTU or BACnet MS/TP
RS485 Wiring