F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page 76
Model F-5500
COMMUNICATIONS
Common
Commands
Common-Practice Commands, Supported Commands
The following common-practice commands are implemented:
34 Write Damping Value
35 Write Range Values
36 Set PV Upper Range Values
37 Set PV Lower Range Values
38 Reset "Configuration Changed" Flag
40 Enter/Exit Fixed Current Mode
44 Write PV Units
45 Trim Loop Minimum
46 Trim Loop Maximum
48 Read Additional Device Status (Command #48 returns 2 bytes of data)
59 Write Number of Response Preambles
Capability Checklist
Manufacturer, model ONICON Inc, F-5500
Device type Transmitter
HART revision 7.1
Device Description available No
Number and type of sensors 1
Number and type of actuators 0
Number and type of host side signals 1 : 4-20mA analog
Number of Device Variables 0
Number of Dynamic Variables 4
Mappable Dynamic Variables No
Number of common-practice
commands
17
Number of device-specific commands 0
Bits of additional device status 8
Alternative operating modes No
Burst mode No
Write-protection Yes
Common-Practice Commands, Unsupported Commands
Burst Mode- This device does not support Burst Mode.
Catch Device Variable- This device does not support Catch Device Variable.
Device-Specific Commands- No Device-Specific commands are implemented.
HART Programming