F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page 82
Model F-5500
TROUBLESHOOTING
Model F-5500
TROUBLESHOOTING
Troubleshooting Zero CAL-CHECK
®
If the F-5500 Meter fails a Zero CAL-CHECK
®
Calibration Validation test, there are a
few reasons that could be the cause:
1. The sensor may be dirty or damaged
Visually inspect the meter for damage. If damage is found, meter may need
to be serviced. Contact ONICON Technical Assistance at 727-447-6140 for
more information
Try cleaning the sensor and try the test again
If the meter fails again, move to #2
2. The sensor may not be properly covered/isolated
Out of Pipe:
Wind currents (fans in room included) could be affecting the sensor
Be sure to use a clean dry plastic bottle to isolate the sensor
In Pipe:
Make sure that there is a "no flow" or zero flow condition on the meter's
sensor
Try the test again
If the meter fails again, move to #3
3. The meter may not have stabilized properly
Make sure the meter is not being affected by vibration or other movement
Allow the meter to stabilize without being moved or touched for 15 minutes
Try the test again
If the meter fails again, contact ONICON Technical Assistance at 727-447-
6140