No. Name Description Range Default
18 AL1-B Alarm 1 threshold, activates
relay 1
by sensor
19 A1Del Alarm 1 Delay on (seconds) 0-999 30
20 A1Off Alarm 1 Delay off (seconds) 0-999 20
21 AL2-B Alarm 2 threshold, activates
relay 2
by sensor
22 A2Del Alarm 2 Delay on (seconds) 0-999 30
23 A2Off Alarm 2 Delay off (seconds) 0-999 20
24 AL3-B Alarm 3 threshold, sounder and
strobe
by sensor
25 A3Del Alarm 3 Delay on (seconds) 0-999 180
26 A3Off Alarm 3 Delay off (seconds) 0-999 20
27 A1Tx Alarm 1 transmit message,
CAN network
0-255 1
28 A1Tx Alarm 1 transmit message,
CAN network
0-255
29 A1Tx Alarm 1 transmit message,
CAN network
0-255
30 A2Tx Alarm 2 transmit message,
CAN network
0-255 2
31 A2Tx Alarm 2 transmit message,
CAN network
0-255
32 BiTx Binary input transmit message
when limit switch is closed,
CAN bus. See 3.2.1
0-255 0
33 A3Tx Alarm 3 transmit message,
CAN network
0-255 3
34 A3Tx Alarm 3 transmit message,
CAN network
0-255
35 A3Tx Alarm 3 transmit message,
CAN network
0-255 0
4.4 List of Settings Sensor B
(lower socket) settings
4.4 List of Settings