No. Name Description Range Default
36 R1Rx Receive message to activate relay 1,
CAN network
0-255 1
37 R2Rx Receive message to activate relay 2,
CAN network
0-255 2
38 R3Rx Receive message to activate sounder
and strobe CAN network
0-255 0
39 Adr Monitor identication address, CAN
network
0-32 0
40 AnZA Accessing this option forces analogue
output A to low for testing with meter
only and no external cables attached.
Use up and down arrows to adjust
lowest setting (2v or 4 ma) and save
41 AnSA Accessing this option forces analogue
output A to high for testing with meter
only and no external cables attached.
Use up and down arrows to adjust
lowest setting (10v or 20 ma)
42 AnZB As option 40 but for output B
43 AnSB As option 41 but for output B
44 Temp Temperature display enable off/on 0/1 0
45 Aud Local audio alarm enable on alarm 3 0/1 1
46 BAC BACnet MSTP mode select
0 = BACnet communication disabled
1 = BACnet communication enabled
2 = BACnet communication enabled
and display all sensors on CAN
network
0/1/2 0
47 BMA BACnet MAC address 127 0
48 BBR BACnet baud rate
0 = 9600
1 = 19200
2 = 38400
3 = 76800
0/1/2/3 3
49 KBL Keyboard lock, blocks access to
options
0/1 0
4.4 List of Settings Continued
General settings