Display is
Inadvertent Start Error.
Flashing “ErP”
The grill was plugged in with the Cook Control switch in the
Smoke position or set to a temperature setting.
Set the Cook Control switch to the Off position.
Display is
Overtemperature Error.
Flashing “ErH”
The grill temperature exceeded 615 degrees and shut off
automatically.
Set the Cook Control switch to the Off position.
Temperature detector wire leads are open.
Check connection at control terminal J1. Fully open contacts
by turning set screw counter clockwise. Reinsert wires and
tighten contacts by turning set screw clockwise.
Check for breaks in the wire throughout the wire run from
detector to control terminal J1.
Temperature detector is defective.
Replace temperature detector.
Control is defective.
Contact Ortech Controls customer service.