26
Unexpected
Auger Idle Fuel Feed Rate is too high.
Temperature is Adjust Smoke Control switch (increase the “P” setting) to
Displayed decrease Idle Fuel Feed Rate.
Auger Idle Fuel Feed Rate is too low.
Adjust Smoke Control switch (decrease the “P” setting) to
increase Idle Fuel Feed Rate.
Grill lid is open.
Close grill lid. Grill is designed to operate with grill lid
closed.
Temperature detector is defective.
Replace temperature detector.
Control is defective.
Contact Ortech Controls customer service.
Grill Temperature
This is normal.
Displayed is Different The displayed temperature is the precise temperature at
Than Dome the temperature detector. The dome thermometer is
Thermometer located in a different position inside the grill.
Displayed
Low grill temperature.
Temperature This is not an error condition and does not affect the
is Flashing operation of the grill. The flashing display is designed to
alert the operator that there is some risk of the fire going
out.
Display Always
Temperature detector wire leads are shorted.
Reads 0 Degrees Check connection at control terminal J1. Fully open contacts
by turning set screw counter clockwise. Reinsert wires and
tighten contacts by turning set screw clockwise.
Check the insulation for shorts throughout the wire run from
detector to control terminal J1.
Temperature detector is defective.
Replace temperature detector.
Control is defective.
Contact Ortech Controls customer service.