Figure 15 - Miscellaneous Screen 2
Force Bulk or Float: Pushing the button under FLOAT or BULK will force the MX60 into that charge state.
Figure 16- Miscellaneous Screen 3
PCB Temperature measurement value used to control the cooling fan’s operation and to provide
overtemperature protection of the internal electronic components. This temperature measurement is not
the actual internal temperature in degrees C or F but is an arbitrary number used for reference. The
lower the number, the higher the temperature. 25 degrees C is approximately a value of 525.
CmpV Temperature compensated Absorb or Float setpoint voltage that the controller is currently using as the
regulation target.
Btmp Battery temperature sensor reference value used to compensate the charging process.
This is an arbitrary number between 0 and 255 and is not the actual temperature in degrees C or F.
GMR Output value of the internal current sensor used to calculate output amps, watts and track the PV output.
Totlkwh Total kW hours accumulated every night from daily KWh. The daily KWH are added to this counter every
night and then cleared. If Zzzz... appears on the STATUS screen, this has already happened.
ClrW Pressing and holding “Clrw” for 4 seconds clears the TotlKWh value.
EndA Normally an absorb charge cycle is terminated because the battery voltage was regulated at the Absorb
setpoint for the maximum time period. Decreasing (DEC) or increasing (INC) sets an optional end cur-
rent level in DC amps. While the MX60 is regulating the charging process in the Absorb stage and the
end current level is reached before the charge timer has reached zero, (ChgT in Figure 14), the MX60
will switch to the Float charge stage. This is an optional setpoint and is not required to be adjusted in
most installations. Zero Absorb end amps is the default and means that this feature is disabled.
PRESS “NEXT” TO
CONTINUE TO
MISCELLANEOUS
SCREEN NO. 3
PRESS “EXIT” TO
RETURN TO THE
MAIN STATUS SCREEN