Aquarea air/water heat pump – Installation manual for compact systems 03 / 2013
4
Location /
Installation
4 13
Location / Installing the device
Location
4 Location / Installing the device
4.1 Location
Weights of the compact units
Aquarea LT single-phase (one fan) 112 kg
Aquarea LT single-phase 153 kg
Aquarea LT three-phase 157 kg
Aquarea T-CAP single-phase 155 kg
Aquarea T-CAP three-phase 158 kg
Aquarea HT n. a.
The installation location must meet the following criteria:
General
 Even and horizontal
 Load-bearing (see device weight table)
 No outside temperature under -20 °C
 ,QVWDOODWLRQDWDKHLJKWVXIÀFLHQWWRSURWHFWDJDLQVWZHDWKHULQÁXHQFHV
such as snow or water levels
 The height difference of the liquid system circuit may not exceed 7 m
 Easy access for maintenance work
 Condensate must drain away easily
 No damage to other objects if water leaks
 If a solar installation is connected, the connection cable between
the solar pump station and the compact unit may not be longer than
10 metres
Minimum clearances
 The minimum clearances (see Figure) must be observed.
Minimum clearances of the compact unit to adjacent walls and objects, indicating the air
ÁRZGLUHFWLRQ
1
Minimum clearance 100 mm
2
Minimum clearance 300 mm
3
Minimum clearance 1,000 mm
2
1
2
3