7 – 25Aquarea air/water heat pump – Installation manual for compact systems 03 / 2013
7
Electrical
installation
Electrical installation
Mains connections
³ Use the following fuses to protect the individual mains connections
(isolating distance between the pins at least 3.0 mm each):
Device name
Fuse
Mains connection
1
Mains connection
2
Mains connection
3
WH-MDC09C3E8, WH-MDF09C3E8,
WH-MXC09D3E8, WH-MXF09D3E8,
WH-MHF09D3E8
20 A 16 A –
WH-MDC12C9E8, WH-MDC14C9E8,
WH-MDC16C9E8, WH-MDF12C9E8,
WH-MDF14C9E8, WH-MDF16C9E8,
WH-MXC12D9E8, WH-MXF12D9E8,
WH-MHF12D9E8
20 A 16 A 16 A
WH-MDF06E3E5, WH-MDC09C3E5,
WH-MDF09C3E5, WH-MDF09E3E5,
WH-MXC09D3E5, WH-MXF09D3E5,
WH-MXC12D6E5, WH-MXF12D6E5,
WH-MHF09D3E5
30 A 30 A –
WH-MDC12C6E5, WH-MDC14C6E5,
WH-MDC16C6E5, WH-MDF12C6E5,
WH-MDF14C6E5, WH-MDF16C6E5,
WH-MHF12D6E5
30 A 30 A 16 A